  • LKX-BT-ER-M10-Stainless-Steel-Threaded-Studs1.jpg
  • LKX-BT-MR-M10-Stainless-Steel-Threaded-Studs2.jpg
  • LKX-BT-ER-M10-Stainless-Steel-Threaded-Studs2.jpg
LKX-BT-ER M10-24-6 SN12-R Stainless Steel Threaded Studs
Specification: LKX-BT-ER M10-24-6 SN12-R
Product No.: 4001007
Material: S31803/1.4462/2205
Base Material Thickness: ≥6mm
Package: 100
Threaded stud for electrical connectors on steel in highly corrosive environments

    LKX-BT-ER M10-24-6 SN12-R Stainless Steel Threaded Studs

    • 产品描述
    • Commodity name: LKX-BT-ER M10-24-6 SN12-R Stainless Steel Threaded Studs
    • 品号: 4001007
    • 规格型号: LKX-BT-ER M10-24-6 SN12-R
    • 材质: S31803/1.4462/2205
    • 基材厚度/高度: Base Material Thickness: ≥6mm
    • 包装: 100

    Threaded stud for electrical connectors on steel in highly corrosive environments

     

     

    Parameter

     

    Performance Indicators LKX-BT-ER M10
    Material Description: Stainless steel
    Ampere-capacity: 50 kA (continuous current 2 ms)
    1500A (continuous current: 1 sec)
    750A (continuous current: 4 sec)
    60A (continuous current)
    Contact Resistance: <5mΩ (IEC60947-7-2)
    Ambient Temperature Range: -55℃ to + 100℃
    Fastener Life: 40 years
    Applicable Base Material Thickness: ≥6 | ≥3
    6mm and above. (Please consult Locke engineers
    for advice on the applicability of thinner materials.)
    Fastening Torque: 5-8Nm
    Recommended Tension: 5.8KN
    Clamping Force: Min. 8Nm, Max. 20Nm

     

     

    Grounding Classification

     

    Contact Resistance: screw cold resistance < 5 mQ (IEC 60947-7-2)

     

    Continuous Current:

    Single point grounding

    Maximum continuous current l=60A
    Recommended copper cable size 10mm²(8AWG).lf the fastener is used outdoors and equipped with the cable that can withstand a temperature of at least 90°C, cables with across-sectional area of up to 16 mm2 can be used.
    (IEC EN 60204-1:2006 & IEC EN 60204-1:1997)
     

     

    Protective Grounding:

    Single point grounding

    Maximum short time current (1 sec.) l=1500A 
    Recommended copper cable size 10mm² (8AWG)
    (IEC 61000-5-2 &lEC EN 60947-7-2 & UL 467)

    Single point grounding

    Double point grounding:
    Maximum short time current (1 sec.) l=2240A
    Recommended copper cable size 16mm² (6AWG)
    (IEC 61000-5-2 & IEC EN 60947-7-2 & UL 467)

     

    Lightning Protection Grounding:

    TypeA

    img

    TypeB

     

    Type A Maximum instantaneous (< 2ms) current l=50KA Contact resistance < 5 mΩ
    Type B Maximum instantaneous (< 2ms) current l=100KA Contact resistance < 5 mΩ
    (IEC EN 50164-1:1999 and lEC EN 50164-1 / prA1:2005)

     

     

    Product Features

     

    1. No rework necessary on coated steel – corrosion protection remains intact

    2. Enhanced safety – allows electrical current to flow through the stud and then discharges it properly into the base material

    3. Portable, cordless system – eliminates the need for long electric supply cords

    4. Fast – ideal for fastening directly to coated or treated steel

    5. Corrosion-resistant – suitable for marine, offshore and petrochemical applications, power plants, etc.

     

    Applications

     

    1. Functional bonding

    2. Protective bonding

    3. Terminal connection

    4. Lightning protection

    5. Bonding and earthing/grounding

     

    lnstallation Steps

     

    Flat Head Stainless Steel Threaded Stud LKX-BT-ER-M10 LKX-BT-ER-M8 LKX-BT-ER-M6

     

    1. Drill a pilot hole

     

    ・Use a DEWALTDCD high speed electric drill and the special drill bit to drill on the base material.

    ・The special drill bit allows the operator to drill to the exact diameter and depth required.

    ・There is no need to remove the paint or coatings from the surface of the base material.

     

    2. Drive the stud

     

    ・Use the innovative LK DX 351 BT to drive the LKX-BT-ER stud in the pilot hole.

    ・The specially designed sealing system for LKX-BT-ER studs keeps out air and moisture.

     

    3. Connect the cable

     

    ・Connect the cable recommended by the project engineer

    ・Tighten the two nuts to the recommended torque

    ・Lock washers to prevent accidental loss.

     